About product
Output power capacity 32.0kWatts / 40.0kVA
Nominal Output Voltage 400V 3PH
Output Voltage Note Configurable for 380: 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load 95.8 %
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains) 47 – 53 Hz for 50 Hz nominal
Output Frequency (not synced) 50Hz +/- 0.1% for 50Hz nominal
Load Crest Factor 3: 1
Topology Double Conversion Online
Waveform type Sine wave
Bypass Built-in Maintenance Bypass, Built-in Static Bypass
Nominal Input Voltage 400V 3PH
Input frequency 40 – 70 Hz (auto sensing)
Input voltage range for main operations 304 – 477V
Efficiency at Full Load 95.8 %
Input Power Factor at Full Load 0.98
Included Battery Modules 4
Typical recharge time 5hour(s)
Interface Port(s) DB-9 RS-232, Smart-Slot
Control panel Multi-function LCD status and control console
Audible Alarm Audible and visible alarms prioritized by severity
1 Year Warranty
APC Smart-UPS VT
Scalable runtime
Allows additional run time to be quickly added as needed.
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
Manageability
SmartSlot
Customize UPS capabilities with management cards.
Network manageable
Provides remote power management of the UPS over the network.
LED status indicators
Quickly understand unit and power status with visual indicators.
InfraStruXure Manager Compatible
Enables centralized management via the APC InfraStruXure Manager.
Programmable frequency
Ensures compatibility with different input frequencies.
Audible alarms
Provides notification of changing utility power and UPS power conditions
LCD display
Alpha-Numeric Display which displays system parameters and alarms.
Serviceability
Shippable with modules installed
Enables pre-installation UPS staging and testing and faster installation.
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
Battery replacement without tools
Enables fast battery replacement, lowering Mean Time to Repair (MTTR).
Protection
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without using the batt